![]() STOPAKEVYCH, A., STOPAKEVYCH, O., TIGAREV, Anatolii, VOROBIOVA, Olena. Automatic Re-tuning of Poor-Performing PI-based Control Systems. In: Problemele Energeticii Regionale, 2024, nr. 2(62), pp. 164-179. ISSN 1857-0070. DOI: https://doi.org/10.52254/1857-0070.2024.2-62.14 |
EXPORT metadate: Google Scholar Crossref CERIF DataCite Dublin Core |
Problemele Energeticii Regionale | ||||||
Numărul 2(62) / 2024 / ISSN 1857-0070 | ||||||
|
||||||
DOI:https://doi.org/10.52254/1857-0070.2024.2-62.14 | ||||||
CZU: 681.51 | ||||||
Pag. 164-179 | ||||||
|
||||||
![]() |
||||||
Rezumat | ||||||
The goal of the work is to create a new method for automatic re-tuning of PI controllers. It is achieved by solving the following problems. The first problem is to develop a method to identify a FOPDT estimation model by analyzing the dynamics of a control loop with a PI controller. The second problem is to demonstrate that the use of the estimated model allows to obtain better processes in control systems with PI controllers by comparing the resulting FOPDT model with a number of reduced models. The third problem is to develop a five-stage algorithm for automatic re-tuning of PI controllers. The fourth problem is to verify the software implementation of the developed algorithm. The most significant result was that the basis for estimating the FOPDT model in a loop with a Ziegler-Nichols tuned PI controller was the estimation the ratio of the delay to the time constant of the FOPDT model based on an assessment of the process overshoot. When the real control plant dynamics did not match with the dynamics of the FOPDT model this way was found effective for finding the optimal tuning of the PI controller. The significance of the results obtained was a structural robustness in case of estimated FOPDT model usage. The effectiveness of the procedure has been demonstrated on both linear and nonlinear models. The developed procedure is proposed to be used to automate the procedure of re-tuning SISO control systems when the control loop performance degradation has been detected. |
||||||
Cuvinte-cheie Control system, automatic re-tuning of the PI controller, FOPDT evaluation model, delay, optimization, structural robustness, control performance, operation, sistem de control SISO, controlere PI, reajustare automată, evaluare model FOPDT, întârziere, optimizare, robustețe structurală, calitate control, funcţionare, система управления, автоматическая перенастройка ПИ-регулятора, оценочная FOPDT модель, запаздывание, оптимизация, структурная робастность, качество управления, эксплуатация |
||||||
|