SM ISO690:2012 МАНУСОВ, Вадим, ПАВЛЮЧЕНКО, Д., АХЬЁЕВ, Дж.. Анализ процессов ограничения токов короткого замыкания трансформатором с высокотемпературными сверхпроводящими обмотками. In: Problemele Energeticii Regionale, 2017, nr. 1(33), pp. 1-7. ISSN 1857-0070. |
EXPORT metadate: Google Scholar Crossref CERIF DataCite Dublin Core |
Problemele Energeticii Regionale | ||||||
Numărul 1(33) / 2017 / ISSN 1857-0070 | ||||||
|
||||||
CZU: 621.314.1 | ||||||
Pag. 1-7 | ||||||
|
||||||
Descarcă PDF | ||||||
Rezumat | ||||||
An important advantage of transformers with high-temperature superconducting winding is their ability to limit the short-circuit currents. The article discusses a physico-mathematical model that analyses transient processes at short-circuit currents in electrical networks containing transformers with a high-temperature superconducting winding. One of the main ideas and objectives of this work is to investigate the process of short-circuit currents limiting by means of a transformer with a hightemperature superconductor winding, which makes it possible to combine two series-connected elements in one device: transformer and a reactor. The effectiveness of this method is due to the fact that when the short-circuit currents exceed the critical value of the temperature of the superconductor winding, it goes to the normal state with high winding resistance for short-circuit currents. It is important to know when a superconductor should go over to a normal state with the loss of superconductivity. For this purpose, a program was developed to determine the amount of heat generated by a short-circuit current flowing before it is disconnected. For a transformer with hightemperature superconducting winding with a capacity of 40 MVA, a short circuit must be eliminated after 0.1 seconds, without switching off the transformer. To limit the short-circuit current; it is intended to use a hybrid winding. The performed assessment showed that the return of the winding to the superconducting state, first, depends on the ratio of the short-circuit currents to the operating current. This is the criterion for the return/non-return to the superconducting state. |
||||||
Cuvinte-cheie трансформатор, сверхпроводниковая обмотка, реактор, предаварийный режим, токи короткого замыкания, энергоэффективность, потери мощности, ограничение |
||||||
|
Google Scholar Export
<meta name="citation_title" content="Анализ процессов ограничения токов короткого замыкания трансформатором с высокотемпературными сверхпроводящими обмотками"> <meta name="citation_author" content="Манусов Вадим"> <meta name="citation_author" content="Павлюченко Д."> <meta name="citation_author" content="Ахьёев Дж."> <meta name="citation_publication_date" content="2017/04/24"> <meta name="citation_journal_title" content="Problemele Energeticii Regionale"> <meta name="citation_volume" content="33"> <meta name="citation_issue" content="1"> <meta name="citation_firstpage" content="1"> <meta name="citation_lastpage" content="7"> <meta name="citation_pdf_url" content="https://ibn.idsi.md/sites/default/files/imag_file/01_Analiza%20proceselor%20de%20limitare%20a%20curentilor%20de%20scurtcircuit%20ale%20transformatorului%20cu%20infasurari.pdf">